Languages

电流钳 & 变送器 Tech specs

Sensors technical specifications

Flux Gate AC/DC Clamps
 
Flux Gate AC/DC Clamps
Hall Effect AC/DC Clamps
Current clamps AC
Current transducers
Rogowsky coils
DS-CLAMP-200DC DS-CLAMP-500DCS DS-CLAMP-500DC DS-CLAMP-1000DC
Type Flux gate Flux gate Flux gate Flux gate
Current Range 200 A DC or AC RMS 500 A DC or AC RMS 500 A DC or AC RMS 1000 A DC or AC RMS
Sensitivity ± 10 mV/A ± 4 mV/A ± 4 mV/A ± 2 mV/A
Bandwidth DC to 500 kHz DC to 200 kHz DC to 100 kHz DC to 20 kHz
TEDS Fully supported Fully supported Fully supported Fully supported
Conductor Position
Sensitivity
max. ± 0.1 % of reading max. ± 0.1 % of reading max. ± 0.2 % of reading max. ± 0.2 % of reading
Zero Offset (+25°C) max. ± 10 mA max. ± 250 mA max. ± 250 mA max. ± 50 mA
Error due Earth
Magnetic Field
max. ± 50 mA max. ± 100 mA max. ± 150 mA max. ± 150 mA
Temp. Coefficient ± 0.01 %/°C ± 0.01 %/°C ± 0.01 %/°C ± 0.01 %/°C
Accuracy Amplitude Phase Error Amplitude Phase Error Amplitude Phase Error Amplitude Phase Error
DC ± 0.3 % rdg.
± 40 mA
± 0.3 % rdg.
± 100 mA
± 0.3 % rdg.
± 100 mA
± 0.3 % rdg.
± 200 mA
to 100 Hz ± 0.3 % rdg.
± 20 mA
± 0.1 ° ± 0.3 % rdg.
± 50 mA
± 0.1 ° ± 0.3 % rdg.
± 50 mA
± 0.1 ° ± 0.3 % rdg.
± 100 mA
± 0.1 °
100 - 500 Hz ± 0.3 % rdg.
± 40 mA
± 0.2 ° ± 0.3 % rdg.
± 100 mA
± 0.2 ° ± 0.3 % rdg.
± 100 mA
± 0.2 ° ± 0.5 % rdg.
± 200 mA
± 0.2 °
500 Hz - 1 kHz ± 0.5 % rdg.
± 40 mA
± 0.5 ° ± 0.5 % rdg.
± 100 mA
± 0.5 ° ± 0.5 % rdg.
± 100 mA
± 0.5 ° ± 1.0 % rdg.
± 200 mA
± 0.5 °
1 kHz - 5 kHz ± 1.0 % rdg.
± 40 mA
± 1.0 ° ± 1.0 % rdg.
± 100 mA
± 1.0 ° ± 1.0 % rdg.
± 100 mA
± 1.5 ° ± 2.0 % rdg.
± 200 mA
± 1.5 °
5 kHz - 10 kHz ± 1.5 % rdg.
± 40 mA
± 1.5 ° ± 1.5 % rdg.
± 100 mA
± 1.5 ° ± 1.5 % rdg.
± 100 mA
± 2.0 ° ± 5.0 % rdg.
± 500 mA
± 2.0 °
10 kHz - 20 kHz ± 5 % rdg.
± 40 mA
± (0.5 + 0.1 f
[kHz]) °
± 5 % rdg.
± 100 mA
± (0.5 + 0.1 f [kHz]) ° ± 5 % rdg.
± 100 mA
± (0.2 f [kHz]) ° ± 30 % rdg.
± 1000 mA
± 10.0 °
20 kHz - 50 kHz ± 5 % rdg.
± 40 mA
± (0.5 + 0.1 f
[kHz]) °
± 5 % rdg.
± 100 mA
± (0.5 + 0.1 f [kHz]) ° ± 10 % rdg.
± 250 mA
± (0.2 f [kHz]) ° ± 30 % rdg.
± 1000 mA
± 10.0 °
50 kHz - 100 kHz ± 15 % rdg.
± 100 mA
± (0.5 + 0.1 f
[kHz]) °
± 15 % rdg.
± 250 mA
± (0.5 + 0.1 f [kHz]) ° ± 30 % rdg.
± 250 mA
± (0.2 f [kHz]) ° ± 30 % rdg.
± 1000 mA
± 10.0 °
100 kHz - 200 kHz ± 5 % rdg.
± 40 mA
± (0.5 + 0.1 f
[kHz]) °
± 30 % rdg.
± 250 mA
± (0.5 + 0.1 f [kHz]) ° / / / /
200 kHz - 300 kHz ± 5 % rdg.
± 40 mA
± (0.5 + 0.1 f
[kHz]) °
/ / / / / /
300 kHz - 500 kHz ± 30 % rdg.
± 100 mA
/ / / / / /
Dimensions [mm] 153 x 67 x 25 153 x 67 x 25 238 x 114 x 35 238 x 114 x 35
Max. Conductor Size 20 mm 20 mm 50 mm 50 mm
Power Supply ± 11 V to ± 15 V ± 11 V to ± 15 V ± 11 V to ± 15 V ± 11 V to ± 15 V
Current Consumption max. 6 VA max. 7 VA max. 7 VA max. 7 VA
Operating Environment Indoors, Pollution Degree II,
altitude up to 2000m
Indoors, Pollution Degree II,
altitude up to 2000m
Indoors, Pollution Degree II,
altitude up to 2000m
Indoors, Pollution Degree II,
altitude up to 2000m
Operating Temp. - 40 °C to + 85 °C - 40 °C to + 85 °C - 40 °C to + 85 °C - 40 °C to + 85 °C
Operating Humidity up to 80 % (not condensing) up to 80 % (not condensing) up to 80 % (not condensing) up to 80 % (not condensing)
Safety Standards EN61010-2-032:2012 EN61010-2-032:2012 EN61010-2-032:2012 EN61010-2-032:2012
EMC Standards EN61326-1:2013 EN61326-1:2013 EN61326-1:2013 EN61326-1:2013
Rohs EN50581:2012 EN50581:2012 EN50581:2012 /
PWR-MCTS2 needed Yes Yes Yes Yes
Compatible amplifiers SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
Cable length 3 m - MCTS to Clamp
0.3 m - Amplifier to MCTS
3 m - MCTS to Clamp
0.3 m - Amplifier to MCTS
3 m - MCTS to Clamp
0.3 m - Amplifier to MCTS
3 m - MCTS to Clamp
0.3 m - Amplifier to MCTS
Data Sheet DS-CLAMP-200DC DS-CLAMP-500DCS DS-CLAMP-500DC DS-CLAMP-1000DC
DS-CLAMP-150DC DS-CLAMP-150DCS DS-CLAMP-1800DC
Type Hall Effect Hall Effect Hall Effect
Current Range 200 A DC or 150 A AC RMS 250 A DC or 150 A AC RMS 1800 A DC or AC RMS
Sensitivity 20 mV/A 20 mV/A 1 mV/A
Accuracy (+25°C) 1 % + 2 mA 1 % + 2 mA
0 - 1000 A: ± 2.5 % of reading ± 0.5 A
1000 - 1500 A: ± 3.5 % of reading
1500 - 1800 A: ± 5 % of reading
Bandwidth DC to 100 kHz DC to 100 kHz DC to 20 kHz
Resolution ± 1 mA ± 1 mA ± 1 mA
TEDS Fully supported Fully supported Fully supported
Conductor Position
Sensitivity
± 0.5 % ± 0.5 % ± 1.5 %
Zero Offset (+25°C) ± 10 mV
max. + 1 mV/°C
± 10 mV
max. + 1 mV/°C
Error du Earth
Magnetic Field
± 0.5 mV ±0.5 mV max. 150 mA
Temp. Coefficient ± 0.02 % of reading / °C ± 0.02 % of reading / °C ± 0.15 % of reading / °C
Zero Auto zero
@ power supply of sensor
Auto zero
@ power supply of sensor
Auto zero via push-button
Dimensions [mm] 205 x 60 x 15 106 x 100 x 25 205 x 60 x 15
Max. Conductor
Size
32 mm 25 mm 32 mm
Power Supply ± 10 V ± 10 V + 9 V
Current Consumption
30 mA + 1mA/A measured 30 mA + 1mA/A measured max. 25mA
Jaws Open Indication
Yes No No
Operating Temp. 0 to + 60 °C 0 to + 60 °C 0 to + 50 °C
Operating Humidity 15 % to 85 %
(not condensing)
15 % to 85 %
(not condensing)
15 % to 85 %
(not condensing)
Safety Standards EN 61010-1:2010
EN 61010-2-032:2012
EN 61010-2-031:2012
EN 61010-1:2010
EN 61010-2-032:2012
EN 61010-2-031:2012
EN 61010-1:2010
EN 61010-2-032:2012
EN 61010-2-031:2012
Safety 300 Vrms CAT III 300 Vrms CAT III 300 Vrms CAT III
EMC Standards EN 61326-2-2:2013 EN 61326-2-2:2013 EN 61326-2-2:2013
PWR-MCTS2 needed
No No No
Compatible Amplifiers
SIRIUS LV / HS-LV / XHS-LV SIRIUS LV / HS-LV / XHS-LV SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
KRYPTON STG, IOLITE STG
DEWE-43
Cable length 3 m 3 m 3 m
Data Sheet DS-CLAMP-150DC DS-CLAMP-150DCS DS-CLAMP-1800DC
DS-CLAMP-5AC DS-CLAMP-15AC DS-CLAMP-200AC DS-CLAMP-1000AC
Type Iron-Core Iron-Core Iron-Core Iron-Core
Range 5 A AC RMS 15 A AC RMS 200 A AC RMS 1000 A AC RMS
Sensitivity 100 mV/A 100 mV/A 10 mV/A 1 mV/A
Accuracy (+25 °C) 5 mA - 0.5 A
± 2 % of reading
0.5 A - 1 A
± 1 % of reading
1 A - 12 A
±0 .5 % of reading
< 1 A
± 2.5 % of reading
1 A - 15 A
± 1 % of reading
0.5 A - 10 A
± 3.5 % of reading
10 A - 100 A
± 2.5 % of reading
100 A - 240 A
± 1 % of reading
< 1 A
± 2 % of reading
10 A - 100 A
± 0.5 % of reading
100 A - 1200 A
± 0.3 % of reading
Phase Error 5 mA - 0.5 A
± 2 °
0.5 A - 1 A
± 1°
1 A - 12 A
± 1 °
< 1 A
± 5 °
1 A - 15 A
± 3 °
0.5 A - 10 A
not specified
10 A - 100 A
≤ 5 °
100 A - 240 A
≤ 2.5 °
< 1 A
not specified
10 A - 100 A
≤ 1 °
100 A - 1200 A
≤ 0.7 °
Bandwidth 2 Hz to 5 kHz 2 Hz to 10 kHz 2 Hz to 10 kHz 2 Hz to 10 kHz
Resolution 0.01 A 0.01 A 0.5 A 0.001 A
TEDS Fully supported Fully supported Fully supported Fully supported
Overload Capability 1.5 x I nominal 1.3 x I nominal 1.3 x I nominal 1.3 x I nominal
Conductor Position
Sensitivity
≤ 0.5 % of reading ≤ 0.5 % of reading ≤ 0.5 % of reading ≤ 0.1 % of reading
Influence of
Crest Factor
≤ 1 % ≤ 3 % ≤ 3 % ≤ 1 %
Error due Earth
Magnetic Field
/ ≤ 15 mV/A @ 50 Hz ≤ 15 mV/A @ 50 Hz ≤ 15 µV/A @ 50 Hz
Temperature
Coefficient
±0.015 % / °C ≤ 0.2 % / 10 °C ≤ 0.2 % / 10 °C ≤ 0.1 % / 10 °C
Influence of
Frequency
/ < 5 % of output signal from
20 Hz ... 1 kHz
< 10 % of output signal from
1 kHz ... 10 kHz
< 3 % of output signal from
20 Hz ... 1 kHz
< 12 % of output signal from
1 kHz ... 10 kHz
< 1 % of output signal from
30 Hz ... 48 Hz
< 0.5 % of output signal from
35 Hz ... 1 kHz
< 1 % of output signal from
1 kHz ... 5 kHz
Dimensions [mm] 102 x 34 x 24 135 x 51 x 30 135 x 51 x 30 216 x 111 x 45

Conductor Diameter
15 mm 20 mm 20 mm 52 mm
Operating
Temperature
-10 °C to +55 °C -40 °C to +70 °C -40 °C to +70 °C -40 °C to +70 °C
Operating
Humidity
up to 85 % (not condensing)
up to 85 % (not condensing) up to 85 % (not condensing) up to 85 % (not condensing)
Safety Standards EN61010-2
EN61010-2-032:2012
EN61010-2
EN61010-2-032:2012
EN61010-2
EN61010-2-032:2012
EN61010-2
EN61010-2-032:2012
Safety CAT III 600V
CAT IV 300V
CAT III 600V
CAT IV 300V
CAT III 600V
CAT IV 300V
CAT III 600V
CAT IV 300V
EMC Standards EN61326-1:2013 EN61326-1:2013 EN61326-1:2013 EN61326-1:2013
PWR-MCTS2 needed No No No No
Compatible Amplifiers
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
Cable length 2 m 1.4 m 1.4 m 1.4 m
Data Sheet DS-CLAMP-5AC DS-CLAMP-15AC DS-CLAMP-200AC DS-CLAMP-1000AC
CT 100 CT 200 CT 400 CT 500 CT 1000 CT 2000
Type Zero-Flux Zero-Flux Zero-Flux Zero-Flux Zero-Flux Zero-Flux
Primary Current Range DC
RMS Sinus
100 A 200 A 400 A 500 A 1000 A 2000 A
Conversion ratio 1:500 1:1000 1:1500 1:750 1:1500 1:2000
Overload Ability Short Time (100 ms)
20 kApk 20 kApk 20 kApk 5000 Apk 5000 Apk 10000 Apk
Max. burden resistor (100 % of Ip) 25 Ω 20 Ω 10 Ω 2.5 Ω 4 Ω 3.5 Ω
di/dt (accurately followed) 100 A/μs 100 A/μs 100 A/μs 100 A/μs 100 A/μs 100 A/μs
Temperature influence 0.2 ppm/K 0.2 ppm/K 0.1 ppm/K < 0.2 ppm/K < 0.3 ppm/K < 0.1 ppm/k
Nominal secondary current 200 mA at 100 A 200 mA at 200 A 266 mA at 400 A 666 mA at 500 A 666 mA at 1000 A 1 A at 2000 A
Bandwidth ( -3 dB) DC ... 2 MHz DC ... 1.1 MHz DC ... 800 kHz DC ... 520 kHz DC ... 440 kHz DC ... 140 kHz
Linearity < 0.002 % < 0.002 % < 0.005 % < 0.003 % < 0.003 % < 0.003 %
Offset < 0.0015 % < 0.0010 % < 0.0008 % < 0.001 % < 0.0012 % < 0.0012 %
Rated isolation voltage RMS,
single isolation CAT III,
pollution deg. 2,
IEC 61010-1 standards,
EN 50178 standards

1000 V

1000 V

1000 V
1000 V 1000 V 1000 V
Test voltage 50 / 60 Hz, 1 min 4.95 kV 4.95 kV 4.95 kV 4.2 kV 4.2 kV 6 kV
Inner diameter 28 mm 28 mm 28 mm 38 mm 38 mm 70 mm
Dimensions 93 x 78.8 x 49.5 94 x 78.8 x 49.5 95 x 78.8 x 49.5 128 x 106 x 54 128 x 106 x 54 231 x 220 x 76
Supply voltage (±5 %) ±15 V ±15 V ±15 V ±15 V ±15 V ±15 V
Operating humidity 20 % to 80 %
(not condensing)
20 % to 80 %
(not condensing)
20 % to 80 %
(not condensing)
20 % to 80 %
(not condensing)
20 % to 80 %
(not condensing)
20 % to 80 %
(not condensing)
Operating temperature - 40 °C to + 85 °C - 40 °C to + 85 °C - 40 °C to + 85 °C - 40 °C to + 85 °C - 40 °C to + 85 °C - 40 °C to + 85 °C
DEWESoft® Shunt 5 Ω 5 Ω 5 Ω 1 Ω 1 Ω 1 Ω
PWR-MCTS2 needed Yes Yes Yes Yes Yes Yes
Compatible amplifiers SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
Cable length 5 m - MCTS to Transducer
0.3 m - Amplifier to MCTS
5 m - MCTS to Transducer
0.3 m - Amplifier to MCTS
5 m - MCTS to Transducer
0.3 m - Amplifier to MCTS
5 m - MCTS to Transducer
0.3 m - Amplifier to MCTS
5 m - MCTS to Transducer
0.3 m - Amplifier to MCTS
5 m - MCTS to Transducer
0.3 m - Amplifier to MCTS
Data Sheet
DS-FLEX-3000-17 DS-FLEX-3000-35 DS-FLEX-3000-35HS DS-FLEX-3000-80 DS-FLEX-30000-120
Type Rogowski coil Rogowski coil Rogowski coil Rogowski coil Rogowski coil
Current Range 3 A, 30 A,
300 A, 3000 A
AC RMS
3 A, 30 A,
300 A, 3000 A
AC RMS
3000 A
AC RMS
3 A, 30 A,
300 A, 3000 A
AC RMS
30 A, 300 A,
3000 A, 30000 A
AC RMS
Sensitivity 1000 mV/A, 100 mV/A,
10 mV/A, 1 mV/A
1000 mV/A, 100 mV/A,
10 mV/A, 1 mV/A
10 mV/A 1000 mV/A, 100 mV/A,
10 mV/A, 1 mV/A
100 mV/A, 10 mV/A,
1 mV/A, 0.1 mV/A
Accuracy
(+25 °C)
≤ 1.5 % ≤ 1.5 % ≤ 1.0 % ≤ 1.5 % ≤ 1.5 %
Phase Error ≤ 1.0 deg ≤ 1.0 deg ≤ 1.0 deg ≤ 1.0 deg ≤ 1.0 deg
Bandwidth 3 A: 10 Hz to 10 kHz
Others: 10 Hz to 20 kHz
3 A: 10 Hz to 10 kHz
Others: 10 Hz to 20 kHz
5 Hz - 1MHz 3 A: 10 Hz to 10 kHz
Others: 10 Hz to 20 kHz
30 A: 10 Hz to 5 kHz
Others: 10 Hz to 20 kHz
TEDS Not supported Not supported Fully supported Not supported Not supported
Noise ≤ 0.04 Arms ≤ 0.04 Arms ≤ 0.04 Arms ≤ 0.04 Arms ≤ 0.04 Arms
Temperature Coefficient
≤ 0.5 % / 10 °C ≤ 0.5 % / 10 °C ≤ 0.5 % / 10 °C ≤ 0.5 % / 10 °C ≤ 0.5 % / 10 °C
Casing
Dimensions
[mm]
120 x 58 x 36 120 x 58 x 36 140 x 64 x 28 120 x 58 x 36 120 x 58 x 36
Coil Length 170 mm 350 mm 350 mm 800 mm 1200 mm
Coil Diameter 45 mm 100 mm 100 mm 250 mm 380 mm
Power Supply +5 V +5 V +9 V +5 V +5 V
Operating
Temperature
- 10 °C to + 55 °C - 10 °C to + 55 °C - 10 °C to + 55 °C - 10 °C to + 55 °C - 10 °C to + 55 °C
Operating
Humidity
up to 90 %
(not condensing)
up to 90 %
(not condensing)
up to 90 %
(not condensing)
up to 90 %
(not condensing)
up to 90 %
(not condensing)
Safety
Standards
EN60529
EN61010-2
EN61010-2-032:2012
EN60529
EN61010-2
EN61010-2-032:2012
EN60529
EN61010-2
EN61010-2-032:2012
EN60529
EN61010-2
EN61010-2-032:2012
EN60529
EN61010-2
EN61010-2-032:2012
Safety CAT IV 600V CAT IV 600V CAT III 1000V CAT IV 1000V CAT IV 1000V
EMC Standards EN61326-1:2013 EN61326-1:2013 EN61326-1:2013 EN61326-1:2013 EN61326-1:2013
PWR-MCTS2 needed No No No No No
Compatible amplifiers SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
SIRIUS LV / HS-LV / XHS-LV
SIRIUS STG / HS-STG
SIRIUS STGM
DEWE 43
Cable length
2.5 m (Extendable to 10 m upon request)
2.5 m (Extendable to 10 m upon request)
2.5 m (Extendable to 10 m upon request)
2.5 m (Extendable to 10 m upon request)
2.5 m (Extendable to 10 m upon request)
Data Sheet DS-FLEX-3000-17 DS-FLEX-3000-35 DS-FLEX-3000-35HS DS-FLEX-3000-80 DS-FLEX-30000-120

Power supply unit technical specifications

SIRIUSi-PWR-MCTS2 / SIRIUSir-PWR-MCTS
SIRIUSi-HD-PWR-MCTS2 / SIRIUSir-HD-PWR-MCTS
Power supply 9 - 36 V DC 9 - 36 V DC
Max power consumption 85 W 85 W
Physical dimensions 265 x 140 x 65 mm 265 x 140 x 65 mm
Operating temperature -20 °C to 50 °C -20 °C to 50 °C
Storage temperature -40 °C to 85 °C -40 °C to 85 °C
Humidity (@ 60 °C) 95 % RH non-condensing 95 % RH non-condensing
Output 4 x Isolated Power supply (1500 V DC, 60 sec) 8 x Isolated Power supply (1500 V DC, 60 sec)
Output voltage ±15 V DC ±15 V DC
Maximum output per channel 20 W 20 W
Short circuit protection indefinite (automatic recovery) indefinite (automatic recovery)
Overload protection 150 % of Iout max. typ 150 % of Iout max. typ